Weil-McLain · Boiler · Heating

Space heating firing and priority switching

SVF 500/600 Series 1

What happens, in order

  1. Flame detected; release boiler to modulation.
  2. If flame is not detected, gas valve turns off, blower runs postpurge, and control restarts the cycle.
  3. If the priority timer runs out, switch to the next priority and start its timer.
  4. When demand is satisfied, go to postpurge.

Timings and thresholds

ItemValue
Retry after failed ignitionFive failures, then control waits 60 minutes before retrying

Applies to: SVF control space heating

Models

SVF 500SVF 600

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 84. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.