Weil-McLain · Boiler · Heating

Space heating call sequence

Ultra Series 4

What happens, in order

  1. Call for heat is detected; the display turns blue.
  2. Start the min/max timers. The highest priority system starts first.
  3. Start circulators for the active priority setup.
  4. Calculate the target temperature. If the sensor is below target, begin the firing sequence.
  5. Drive the blower to ignition speed for prepurge.
  6. For multiple boilers or heat sources, start the additional-heat timer. Type 1 starts immediately; type 2 activates the other source only after the timer; type 3 is the lead boiler and sends the 0-10 VDC signal after the timer; type 4 starts on the lead signal.
  7. After prepurge, activate the gas valve and ignition spark for the ignition period.
  8. Stop the spark and check for a flame signal at the electrode.
  9. When flame is detected, hold at low fire, then release to modulation.
  10. If the priority timer expires, switch to the next priority.
  11. When demand is satisfied, go to postpurge.

Timings and thresholds

ItemValue
Low-fire hold after flame detected (space heating)1 minute
Wait after 5 failed ignition attempts before retry60 minutes

Applies to: Space heating, all Ultra models

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.