Weil-McLain · Boiler · Standby/shutdown
Shutdown when thermostat is satisfied or limit trips
What happens, in order
- When the thermostat opens, the pilot and main gas valves close.
- The inducer runs for a 15-second postpurge.
- The circulator shuts off.
- If a limit control shuts the boiler down, the gas valves close and the inducer runs a 15-second postpurge while the circulator keeps running.
- The boiler is now in the off cycle.
- Repeat the call-for-heat cycle several times to verify operation, then return the thermostat to its normal setting.
Timings and thresholds
| Item | Value |
|---|---|
| Postpurge after thermostat satisfied | 15 seconds |
| Postpurge after limit shutdown | 15 seconds |
Applies to: CGi Series 5 boilers
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 Boiler Manual, p. 45. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.