Weil-McLain · Boiler · Pump/purge

Purge air from water system

Ultra Series 4

What happens, in order

  1. Connect a hose to the purge valve and route it to a drain where flow can be seen.
  2. Close the boiler or system isolation valve between the purge valve and fill connection.
  3. Close zone isolation valves.
  4. Open the quick-fill valve on the cold make-up line.
  5. Open the purge valve.
  6. Open one zone isolation valve at a time and run water until no air flow is seen; close it and move to the next zone.
  7. Close the quick-fill and purge valves, remove the hose and open all isolation valves.
  8. Watch system pressure rise to the correct cold-fill pressure.
  9. Vent remaining air from the manual air vents, lowest floor first, closing each when water squirts out.
  10. Open the automatic air vent one turn if the system uses a diaphragm or bladder tank, then purge it.
  11. Refill to the correct pressure.

Applies to: Ultra Series 4 hydronic systems

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 36. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.