Weil-McLain · Boiler · Pump/purge
Purge air from the water system
What happens, in order
- Connect a hose to the purge valve and route it to a drain where the water can be seen.
- Close the boiler or system isolation valve between the purge valve and the fill connection.
- Close the zone isolation valves.
- Open the quick-fill valve on the cold water make-up line.
- Open the purge valve.
- Open one zone isolation valve at a time and run water until no air flow is seen, then close it.
- Repeat for all zones and for the boiler and its internal piping.
- Close the quick-fill and purge valves, remove the hose and open all isolation valves.
- Watch system pressure rise to correct cold-fill pressure.
- Open manual air vents one at a time from the lowest floor until water squirts out, then close them.
- On diaphragm or bladder tank systems, open the automatic air vent one turn.
- Refill to correct pressure.
Applies to: ECO Tec Series 3 80/110/150/199
Models
80110150199
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 130-131. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.