Weil-McLain · Boiler · Pump/purge
Purge air from the hydronic side
What happens, in order
- Fill the system with water.
- Shut off the gas valve and turn the power on.
- Call for DHW by opening a faucet. The circulator runs and circulates water through the boiler.
- Close the faucet when complete.
- Temporarily add a jumper to the boiler thermostat input to create a CH call. This moves the internal 3-way valve and circulates water through the primary/secondary piping.
- Remove the jumper when complete.
- Repeat as needed to remove all air.
- Clear all error codes from the control.
Applies to: Tankless DHW and combi purge
Models
110 C150 C199 C
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 52. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.