Weil-McLain · Boiler · Pump/purge

Purge air from the hydronic side

ECO Tec Series 3

What happens, in order

  1. Fill the system with water.
  2. Shut off the gas valve and turn the power on.
  3. Call for DHW by opening a faucet. The circulator runs and circulates water through the boiler.
  4. Close the faucet when complete.
  5. Temporarily add a jumper to the boiler thermostat input to create a CH call. This moves the internal 3-way valve and circulates water through the primary/secondary piping.
  6. Remove the jumper when complete.
  7. Repeat as needed to remove all air.
  8. Clear all error codes from the control.

Applies to: Tankless DHW and combi purge

Models

110 C150 C199 C

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 52. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.