Weil-McLain · Boiler · Domestic hot water
Preheat and ECO Boost operation on combi models
What happens, in order
- In standby, if boiler out falls below preheat temp minus preheat circ diff, the boiler circulator starts.
- Preheat checks the preheat on diff to decide whether to stop or fire the burner.
- Burner modulates toward preheat temp and shuts off when boiler out exceeds preheat temp plus preheat off diff.
- After a combi DHW call ends, if boiler out is below ECO Boost setpoint minus ECO Boost on diff, the burner keeps firing.
- Burner shuts off when boiler out exceeds ECO Boost setpoint plus ECO Boost off diff.
Applies to: Combi models
Models
ECO Tec 110 CombiECO Tec 150 CombiECO Tec 199 Combi
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 119. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.