Weil-McLain · Boiler · Startup
Power-up check
What happens, in order
- Check the boiler model on the power-up screen. If it is wrong, turn the boiler off and change it in the settings (p. 75).
- Confirm each connected sensor appears on the power-up screen.
- If a sensor is missing, check its connection, turn off power, and restart.
Applies to: SVF 1500-3000 Series 1 with Unity control
Models
SVF 1500SVF 2000SVF 2500SVF 3000
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SVF 1500-3000 Series 1 boiler manual, p. 68. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.