Weil-McLain · Boiler · Startup

Power-up check

SVF Series 1

What happens, in order

  1. Check the boiler model on the power-up screen. If it is wrong, turn the boiler off and change it in the settings (p. 75).
  2. Confirm each connected sensor appears on the power-up screen.
  3. If a sensor is missing, check its connection, turn off power, and restart.

Applies to: SVF 1500-3000 Series 1 with Unity control

Models

SVF 1500SVF 2000SVF 2500SVF 3000

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 68. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.