Weil-McLain · Boiler · Ignition

Pilot ignition sequence

CGi Series 5

What happens, in order

  1. On a call for heat, the control starts the inducer and shows Pre-Purge.
  2. The pre-purge timer starts once the air pressure circuit closes.
  3. When pre-purge is complete, the control energizes the pilot valve and starts spark ignition.
  4. The control starts the pilot flame-sense timer and monitors flame sense to verify the pilot is lit.
  5. If the pilot flame-sense timer expires without an acceptable flame, the control removes power from the pilot valve, runs an inter-purge, and decides whether a restart is possible.
  6. When the pilot is proven, the control energizes the main gas valve.
  7. If flame is not proven within the verification interval, the control turns off both the main and pilot gas valves.

Timings and thresholds

ItemValue
Pre-purge timer15 seconds, starts when the air pressure circuit closes
Pilot flame-sense timer15 seconds

Codes you may see during this

Pre-Purge

Applies to: CGi-25 to CGi-8

Models

CGi-25 to CGi-8

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 60. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.