Weil-McLain · Boiler · Ignition

Pilot ignition and shutdown sequence

CGi Series 5

What happens, in order

  1. On a heat call, the control starts the system circulator and the inducer.
  2. The inducer purges the boiler flue passages before ignition.
  3. The pilot valve opens and pilot spark starts.
  4. The control allows up to 15 seconds to prove pilot flame.
  5. If pilot is not proven in 15 seconds, the gas valve closes, a 15-second postpurge runs, and a new trial starts. This repeats until pilot is proven or power is lost.
  6. Once pilot is proven, the gas valve opens to light the main burner.
  7. When the thermostat is satisfied, the gas valve closes, the inducer runs a 15-second postpurge, and the boiler waits for the next call.

Timings and thresholds

ItemValue
Pilot flame trial15 seconds
Postpurge after failed pilot trial or heat call end15 seconds
Circulator exercise after 30 days of no operation30 seconds run
Circulator run in low water condition with heat callUp to 15 minutes

Applies to: CGi-25 to CGi-8

Models

CGi-25CGi-3CGi-4CGi-5CGi-6CGi-7CGi-8

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.