Weil-McLain · Boiler · Ignition
Pilot ignition and shutdown sequence
What happens, in order
- On a heat call, the control starts the system circulator and the inducer.
- The inducer purges the boiler flue passages before ignition.
- The pilot valve opens and pilot spark starts.
- The control allows up to 15 seconds to prove pilot flame.
- If pilot is not proven in 15 seconds, the gas valve closes, a 15-second postpurge runs, and a new trial starts. This repeats until pilot is proven or power is lost.
- Once pilot is proven, the gas valve opens to light the main burner.
- When the thermostat is satisfied, the gas valve closes, the inducer runs a 15-second postpurge, and the boiler waits for the next call.
Timings and thresholds
| Item | Value |
|---|---|
| Pilot flame trial | 15 seconds |
| Postpurge after failed pilot trial or heat call end | 15 seconds |
| Circulator exercise after 30 days of no operation | 30 seconds run |
| Circulator run in low water condition with heat call | Up to 15 minutes |
Applies to: CGi-25 to CGi-8
Models
CGi-25CGi-3CGi-4CGi-5CGi-6CGi-7CGi-8
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.