Weil-McLain · Boiler · Ignition

Pilot ignition and burner start on heat call

CGi Series 5

What happens, in order

  1. On a room thermostat call, the control module starts the system circulator and the inducer.
  2. The inducer runs long enough to purge the flue passages.
  3. The pilot valve opens and pilot ignition spark starts.
  4. Pilot flame must be proven within 15 seconds.
  5. If no pilot flame is sensed, the gas valve closes, a 15-second postpurge runs, and a new cycle starts; this repeats until the pilot lights or power is cut.
  6. Once pilot flame is proven, the gas valve opens to light the main burner.
  7. When the thermostat is satisfied, the gas valve closes and the inducer runs a 15-second postpurge before the next call.

Timings and thresholds

ItemValue
Pilot flame establishment window15 seconds
Postpurge after failed pilot or heat call end15 seconds

Applies to: CGi Series 5 with spark ignition

Models

CGi-25 to CGi-8

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 Gas-Fired Water Boiler — Boiler Manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.