Weil-McLain · Boiler · Heating
Outdoor reset supply target
What happens, in order
- Set Supply Max to the required supply temperature at design maximum heat loss.
- Set Supply Min to the lowest desired supply temperature.
- Set OD Reset Max, the outdoor temperature where target reaches Supply Min. Factory default is 70 °F.
- Set OD Reset Min to the outdoor design temperature for the site. Factory default is 0 °F. Target reaches Supply Max here.
- The control sets target temperature between these points based on outdoor temperature.
Applies to: SlimFit 1000-2000 Series 2 boilers with outdoor sensor and ODT target
Models
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 64. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.