Outdoor reset supply target

SlimFit Series 2

What happens, in order

  1. Set Supply Max to the required supply temperature at design maximum heat loss.
  2. Set Supply Min to the lowest desired supply temperature.
  3. Set OD Reset Max, the outdoor temperature where target reaches Supply Min. Factory default is 70 °F.
  4. Set OD Reset Min to the outdoor design temperature for the site. Factory default is 0 °F. Target reaches Supply Max here.
  5. The control sets target temperature between these points based on outdoor temperature.

Applies to: SlimFit 1000-2000 Series 2 boilers with outdoor sensor and ODT target

Models

SF1000SF1500SF2000

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 64. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.