Installation sequence - vertical vent / sidewall air

ECO Tec Series 3

What happens, in order

  1. Read this manual and pages 25 through 27 before starting vent/air work.
  2. Install the boiler where vent and air piping can route to the selected locations.
  3. Confirm the vertical termination location meets the clearances in the manual figure.
  4. Use only listed vent materials and add adapters where required; keep lengths within the allowed maximum.
  5. Prepare the vertical vent penetration and the sidewall air penetration and secure components.
  6. Terminate the air piping in a 90-degree down-turned elbow and the vent piping in an upward-pointing coupling.
  7. Install vent and air piping to the terminations, sloping horizontal runs down toward the boiler at least 1/4 in per foot.
  8. Install pipe supports every 5 ft and a hanger within 6 in of any upturn.
  9. Insert piping through penetrations and secure the termination fittings.
  10. Maintain clearances and fit bird screens to both terminations.

Timings and thresholds

ItemValue
Horizontal pipe slope1/4 in per foot down toward boiler
Pipe support spacingmax 5 ft apart
Adjacent air inlets (multiple boilers)at least 6 in apart
Adjacent vent terminations (multiple boilers)at least 6 in apart

Applies to: Vertical vent with sidewall air

Models

80/110/150/199 Series 3

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Boiler Manual, p. 43. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.