Weil-McLain · Boiler · Other

Installation sequence - direct vent vertical concentric

ECO Tec Series 3

What happens, in order

  1. Read this manual and pages 25 through 28 before starting vent/air work.
  2. Install the boiler where all vent and air piping can route to the termination location.
  3. Confirm the vertical termination location meets the clearances in the manual figure and multi-boiler spacing figure.
  4. Use only listed vent materials and add pipe adapters where required.
  5. Check that total vent and air lengths do not exceed the allowed maximum.
  6. Assemble and install the concentric termination before connecting piping from the boiler.
  7. Prepare the vertical penetration, assemble the kit and secure penetration components with supports.
  8. Install vent and air piping to the termination, sloping horizontal runs down toward the boiler at least 1/4 in per foot.
  9. Install pipe supports every 5 ft on horizontal and vertical runs.
  10. Install a hanger support within 6 in of any upturn in the piping.
  11. Use sweep elbows only. Do not use short radius elbows in vent or air piping.

Timings and thresholds

ItemValue
Horizontal pipe slope1/4 in per foot down toward boiler
Pipe support spacingmax 5 ft apart, horizontal and vertical
Hanger support from upturnwithin 6 in

Applies to: Vertical concentric direct vent

Models

80/110/150/199 Series 3

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Boiler Manual, p. 41. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.