Weil-McLain · Boiler · Heating

Heat demand to output energising

SVF 500/600 Series 1

What happens, in order

  1. An input (Input 1 to 4) closes its dry contact to call for heat or indirect DHW.
  2. The control checks that the priority assigned to that input/output pair is active.
  3. If the priority is active, the matching 120 Vac output (Output 1 to 4) energises.
  4. The zone can call, but its pump does not run unless the boiler is already running on that system and priority.
  5. With 0-10 Vdc modulation, the boiler starts at 0.9 Vdc and stops at 0.5 Vdc, and Output 2 follows the heat demand.

Timings and thresholds

ItemValue
Remote modulation start level0.9 Vdc
Remote modulation stop level0.5 Vdc

Applies to: SVF 500/600 Series 1 boilers

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual 550-100-273/1224, pp. 72, 77. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.