Weil-McLain · Boiler · Ignition

Heat call and pilot ignition sequence

CGi Series 5

What happens, in order

  1. On a room thermostat call, the control module starts the system circulator and the inducer.
  2. The inducer runs long enough to purge the boiler flue passages.
  3. The control module opens the pilot valve and starts pilot ignition spark.
  4. The control module allows up to 15 seconds to prove pilot flame.
  5. If no pilot flame is sensed in 15 seconds, the gas valve closes and the inducer runs a 15-second postpurge, then a new cycle starts.
  6. The retry cycle repeats until pilot flame is proven or power is interrupted.
  7. Once pilot flame is proven, the gas valve opens to light the main burner.

Timings and thresholds

ItemValue
Pilot flame proving window15 seconds
Postpurge after failed pilot attempt15 seconds
Inducer purge before pilot valve opensRuns long enough to purge flue passages (no time given)

Applies to: CGi Series 5 gas ignition

Models

CGi-25 to CGi-8

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.