Weil-McLain · Boiler · Freeze protection

Freeze protection operation

ECO Tec Series 3

What happens, in order

  1. Heat exchanger sensors detect a temperature below 45 F.
  2. Boiler fires at low fire and starts the selected circulators.
  3. If temperature drops below 40 F, the burner stays on.
  4. When temperature rises above 48 F, circulators and burner turn off.

Timings and thresholds

ItemValue
Freeze protect startbelow 45 F
Burner onbelow 40 F
Circulators and burner offabove 48 F

Applies to: ECO Tec control with freeze protect circs enabled

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 116. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.