Weil-McLain · Boiler · Freeze protection

Freeze protection circulator operation

Ultra Series 4

What happens, in order

  1. If the heat exchanger sensor reads below 40°F, the boiler fires at low fire.
  2. The circulators selected for freeze protection start.
  3. When the heat exchanger temperature rises above 45°F, the circulators turn off.

Timings and thresholds

ItemValue
Freeze protection on thresholdbelow 40°F
Freeze protection off thresholdabove 45°F

Applies to: Ultra U-Control freeze protection circulators

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 101 and p. 102. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.