Weil-McLain · Boiler · Freeze protection
Freeze protection circulator operation
What happens, in order
- If the heat exchanger sensor reads below 40°F, the boiler fires at low fire.
- The circulators selected for freeze protection start.
- When the heat exchanger temperature rises above 45°F, the circulators turn off.
Timings and thresholds
| Item | Value |
|---|---|
| Freeze protection on threshold | below 40°F |
| Freeze protection off threshold | above 45°F |
Applies to: Ultra U-Control freeze protection circulators
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 101 and p. 102. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.