Flame detected and modulation, with retry logic

ECO Tec Series 3

What happens, in order

  1. When flame is detected, the boiler releases to modulation for space heating or DHW.
  2. If the priority timer runs out, the control switches to the next priority and starts that priority's timer.
  3. If flame is not detected, the gas valve closes, the blower runs postpurge, and the control starts the cycle again.
  4. If flame is missed 5 times, the control waits 60 minutes before trying again.

Timings and thresholds

ItemValue
Ignition retry lockoutafter 5 failed ignitions, wait 60 minutes

Applies to: Space heating and DHW heating on ECO Tec Series 3

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 84. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.