Fill the system with water and purge air
What happens, in order
- Close manual and automatic air vents and the boiler drain cock.
- Fill to correct system pressure; typical cold fill for a residential system is 12 psi.
- Connect a hose to the purge valve at the drain valve and route it where water can drain and be seen.
- Close the boiler or system isolation valve between the purge valve and the fill connection.
- Close zone isolation valves.
- Open the quick-fill valve on the cold makeup line.
- Open the purge valve.
- Open one zone isolation valve at a time, let water run until no air flow is seen, then close it and move to the next zone.
- Close the quick-fill valve and purge valve and remove the hose.
- Open all isolation valves and watch system pressure rise to correct cold-fill pressure.
- After operation, bleed residual air with manual air vents.
- If no purge valves are installed, open manual vents one at a time starting on the lowest floor and close each when water squirts out.
- Open the automatic air vent (diaphragm or bladder tank systems) one turn.
- Open other vents starting on the lowest floor until water squirts out, then refill to correct pressure.
Applies to: EG / PEG water boilers
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 boiler manual, p. 57. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.