Fill and purge the system with water
What happens, in order
- Close the manual and automatic air vents and the boiler drain cock.
- Fill to correct system pressure. Typical cold-fill pressure for a residential system is 12 psi.
- Connect a hose to a purge valve and route it to a place where water can drain and be seen.
- Close the boiler or system isolation valve between the purge valve and the fill connection.
- Close the zone isolation valves.
- Open the quick-fill valve on the cold water makeup line.
- Open the purge valve.
- Open one zone isolation valve at a time and run water until no air flow is seen. Close it, then go to the next zone.
- Close the quick-fill valve and purge valve, remove the hose, open all isolation valves, and confirm pressure rises to correct cold-fill pressure.
- Open the automatic air vent one turn if the system uses a diaphragm or bladder expansion tank.
- Vent air at each manual vent, starting from the lowest floor, until water squirts out, then refill to correct pressure.
Applies to: CGi-25 to CGi-8
Models
CGi-25 to CGi-8
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 boiler manual, p. 62. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.