Weil-McLain · Boiler · Other

Dual pressure switch operation (CGi-4, -7 and -8 only)

CGi Series 5

What happens, in order

  1. With the inducer on, the air pressure switch and high fire pressure switch are both closed.
  2. The air pressure switch closes the safety circuit for the Unity CI control.
  3. The high fire pressure switch completes the circuit to the high fire input of the gas valve, so the valve can deliver full manifold pressure.

Applies to: CGi-4, CGi-7, CGi-8

Models

CGi-4CGi-7CGi-8

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 60. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.