Weil-McLain · Boiler · Other
Direct vent sidewall termination installation sequence
What happens, in order
- Step 1 Install the boiler.
- Step 2 Choose the wall penetration location for each termination and prepare the wall penetrations before installing air and vent piping.
- Step 3 Install air and vent piping from the boiler to the termination. Put a hanger support within 6 in of any upturn and slope horizontal piping down toward the boiler.
- Step 4 Connect the vent and air piping at the boiler per the manual.
- Finish by attaching external pipe and fittings, supporting vertical runs with brackets, and installing the termination assembly as described in the manual.
- If using stainless steel pipe, install the required adapter at each boiler fitting.
Timings and thresholds
| Item | Value |
|---|---|
| Horizontal air and vent pipe slope | at least 1/4 in per ft toward the boiler |
| Hanger support distance from any upturn | within 6 in |
Applies to: Direct vent sidewall termination
Models
SF-550SF-750
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 38. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.