Weil-McLain · Boiler · Domestic hot water

DHW heating sequence

Ultra Series 4

What happens, in order

  1. Call for DHW shows a purple display backlight.
  2. Blower goes to ignition speed for prepurge, then ignition begins.
  3. When flame is detected, the boiler goes to modulation immediately (no low-fire hold).
  4. If flame is not detected, the gas valve closes, blower postpurges and the cycle restarts; after 5 failures the control waits 60 minutes.
  5. If the priority timer runs out, switch to the next priority.
  6. When demand is satisfied, go to postpurge.

Timings and thresholds

ItemValue
Retry wait after 5 failed ignitions60 minutes

Applies to: DHW priority on U-Control

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.