Weil-McLain · Boiler · Domestic hot water
DHW heating sequence
What happens, in order
- Call for DHW shows a purple display backlight.
- Blower goes to ignition speed for prepurge, then ignition begins.
- When flame is detected, the boiler goes to modulation immediately (no low-fire hold).
- If flame is not detected, the gas valve closes, blower postpurges and the cycle restarts; after 5 failures the control waits 60 minutes.
- If the priority timer runs out, switch to the next priority.
- When demand is satisfied, go to postpurge.
Timings and thresholds
| Item | Value |
|---|---|
| Retry wait after 5 failed ignitions | 60 minutes |
Applies to: DHW priority on U-Control
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.