DHW heating call sequence
What happens, in order
- Call for DHW is detected; the display turns purple.
- Start the circulators and timers for the DHW priority.
- Calculate the target temperature and begin firing if below target.
- When flame is detected, release to modulation immediately.
- If the priority timer expires, switch to the next priority.
- When demand is satisfied, go to postpurge.
Timings and thresholds
| Item | Value |
|---|---|
| Retry after 5 failed ignition attempts | 60 minutes wait before retry |
Applies to: DHW heating, all Ultra models
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.