Weil-McLain · Boiler · Domestic hot water
DHW heating and priority switching
What happens, in order
- Flame detected; release boiler to modulation.
- If flame is not detected, gas valve turns off, blower runs postpurge, and control restarts the cycle.
- If the priority timer runs out, switch to the next priority and start its timer.
- When demand is satisfied, go to postpurge.
Timings and thresholds
| Item | Value |
|---|---|
| Retry after failed ignition | Five failures, then control waits 60 minutes before retrying |
Applies to: SVF control DHW heating
Models
SVF 500SVF 600
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 84. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.