Weil-McLain · Boiler · Standby/shutdown

Demand satisfied and return to standby

SlimFit Series 3

What happens, in order

  1. Demand is satisfied when the temperature reaches target or the limit setting.
  2. Close the gas valve.
  3. Run the blower at ignition speed for postpurge.
  4. Return to standby after purge. Standby shows dots toggling, or a wrench symbol if maintenance is due.

Applies to: SlimFit 550/750 Series 3 with Control

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 66. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.