Weil-McLain · Boiler · Heating

Control sequence of operation (call for heat to modulation)

SlimFit Series 2

What happens, in order

  1. Power up the screen lists detected sensors; confirm the model and that all sensors show.
  2. Standby no call for heat; the display cycles dots and shows a wrench if maintenance is due.
  3. Blower on call for heat detected; start circulators for the priority; calculate target; if sensor temp is below target, begin firing.
  4. Wait for the closure switch, if used; blower goes to purge speed for prepurge; check min air flow switch.
  5. Ignition after prepurge, go to ignition speed; open gas valve and spark; spark stops and the flame rod checks for flame.
  6. Space heating or DHW heating once flame is detected, release to modulation; switch priority when the priority timer ends.
  7. Blower off demand satisfied; close gas valve; blower runs ignition speed for postpurge; return to standby.
  8. If no flame is detected, the gas valve closes, postpurge runs and the cycle restarts. After 2 failures the control locks out.
  9. Maintenance the display turns blue during standby when the maintenance timer expires; the boiler still runs.
  10. Error or fault display turns red; a flashing display means lockout.
  11. WWSD space heating is blocked when outdoor temperature is above the WWSD setting; DHW is not affected.

Timings and thresholds

ItemValue
Closure switch proof window4 minutes
Flame failure retries before lockout2 failures

Applies to: SF1000L/R, SF1500L/R, SF2000L/R

Models

SF1000SF1500SF2000

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 62. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.