Weil-McLain · Boiler · Ignition
Control module ignition and pilot sequence
What happens, in order
- On a room thermostat call for heat, the control module starts the system circulator and the inducer.
- The inducer purges the boiler flue passages before ignition begins.
- The control module opens the pilot valve and activates pilot ignition spark.
- If pilot flame is not proven within the allowed window, the gas valve closes, a postpurge runs, and a new attempt starts.
- This retry cycle repeats until pilot flame is established or power is interrupted.
- Once pilot flame is proven, the control module opens the gas valve to light the main burner.
- When the thermostat is satisfied, the gas valve closes and the inducer runs a postpurge before waiting for the next call.
Timings and thresholds
| Item | Value |
|---|---|
| Pilot flame establishment window | 15 seconds |
| Postpurge after failed pilot attempt | 15 seconds |
| Postpurge after thermostat is satisfied | 15 seconds |
Applies to: CGi Series 5 boiler with spark-ignited pilot
Models
CGi Series 5 sizes 25-8
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 boiler manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.