Circulator operation in direct connect piping
What happens, in order
- By default, the internal boiler circulator turns on for any configured heating call or DHW call.
- If an indirect tank is used (Figure 65, item 28), set up a zone valve to turn on when the indirect tank input is active.
- Assign zone valve end switches to Input 1 for the indirect tank (Priority 1 for DHW) and Inputs 2, 3 and 4 for heating zones (Priority 2 or 3).
Applies to: Direct connect, single boiler, 80/110/150
Models
ECO Tec 80ECO Tec 110ECO Tec 150
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 56. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.