Weil-McLain · Boiler · Freeze protection

Circulator freeze protection

CGi Series 5

What happens, in order

  1. Sensor reads below the on threshold.
  2. Control energizes the circulator.
  3. Circulator stays on until the sensor rises above the off threshold.
  4. Control de-energizes the circulator.
  5. A call for heat during this time proceeds normally.

Timings and thresholds

ItemValue
Circulator on when sensor below40°F
Circulator off when sensor above45°F

Applies to: CGi Series 5 with Freeze Protect enabled

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGi Series 5 boiler manual, p. 54. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.