Check flame and combustion, then adjust gas valve

SVF Series 1

What happens, in order

  1. Call for heat on one of the heat demand inputs.
  2. Press and hold the up and down arrow keys for 7 seconds to open the contractor menus.
  3. Use DIAGNOSTICS to reach Manual Test Mode and force the high fire rate.
  4. Remove the flue temperature sensor and install a 1/4 in BSP hose barb and hose. Insert the combustion probe and test CO2 (or O2) and CO.
  5. Compare results with the CO2 values in Figure 80. Adjust only if results are not acceptable.
  6. Reinstall the flue temperature sensor before leaving the boiler. Leaving it out can spill flue gas into the room.
  7. To adjust at high fire, go to the high fire RPM from Figure 79 and let the boiler stabilize, then read CO2.
  8. If CO2 is high, turn the throttle screw toward minus with a small flat screwdriver in 1/8 turn steps.
  9. If CO2 is low, turn the throttle screw toward plus in 1/8 turn steps.
  10. Repeat until the target CO2 is reached, then check combustion at low fire too.

Timings and thresholds

ItemValue
Hold arrows to open contractor menus7 seconds
Hold arrows to clear history counters5 seconds

Applies to: Combustion test and gas valve adjustment

Models

SVF 1500SVF 2000SVF 2500SVF 3000

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 88-89. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.