Check flame and combustion, then adjust gas valve
What happens, in order
- Call for heat on one of the heat demand inputs.
- Press and hold the up and down arrow keys for 7 seconds to open the contractor menus.
- Use DIAGNOSTICS to reach Manual Test Mode and force the high fire rate.
- Remove the flue temperature sensor and install a 1/4 in BSP hose barb and hose. Insert the combustion probe and test CO2 (or O2) and CO.
- Compare results with the CO2 values in Figure 80. Adjust only if results are not acceptable.
- Reinstall the flue temperature sensor before leaving the boiler. Leaving it out can spill flue gas into the room.
- To adjust at high fire, go to the high fire RPM from Figure 79 and let the boiler stabilize, then read CO2.
- If CO2 is high, turn the throttle screw toward minus with a small flat screwdriver in 1/8 turn steps.
- If CO2 is low, turn the throttle screw toward plus in 1/8 turn steps.
- Repeat until the target CO2 is reached, then check combustion at low fire too.
Timings and thresholds
| Item | Value |
|---|---|
| Hold arrows to open contractor menus | 7 seconds |
| Hold arrows to clear history counters | 5 seconds |
Applies to: Combustion test and gas valve adjustment
Models
SVF 1500SVF 2000SVF 2500SVF 3000
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 88-89. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.