Weil-McLain · Boiler · Heating

Central heat call with residual heat recovery and delayed ignition

CGi Series 5

What happens, in order

  1. Thermostat calls for heat and the circulator starts.
  2. Control measures how the boiler water temperature changes.
  3. Control calculates a delay based on these readings.
  4. Burner only fires after the control decides residual hot water cannot satisfy the demand.
  5. ECONOMY SETTING sets how long the residual heat attempt may run.

Timings and thresholds

ItemValue
Minimum delay (ECONOMY SETTING 10%)Gas enabled immediately
Maximum delay (ECONOMY SETTING 100%)Up to 120 seconds

Applies to: CGi Series 5 all models

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGi Series 5 boiler manual, p. 51, 55. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.