Call for heat with residual-heat delay

CGi Series 5

What happens, in order

  1. Central heat call starts and the circulator is energized.
  2. The control circulates the water already in the system and measures how the boiler water temperature changes.
  3. The control calculates a delay from those measurements.
  4. If the hot water in the system cannot satisfy the demand, the boiler is turned on after the delay.
  5. The ECONOMY ADJUST setting scales the delay; at 10% the delay is the shortest possible.

Timings and thresholds

ItemValue
Economy setting at minimum (10%)Gas heat enabled immediately when the thermostat demand starts
Economy setting at maximum (100%)Gas heat enable may be delayed up to 120 seconds

Applies to: CH call with economy setting; not used when ODR is enabled

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 Gas-Fired Water Boiler Boiler Manual, p. 51, 55. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.