Weil-McLain · Boiler · Heating

Call for heat through ignition to flame

SVF Series 1

What happens, in order

  1. On a call for heat, the display turns blue for space heating or purple for DHW.
  2. Start the min/max timers if more than one system is calling. Highest priority starts first.
  3. Start the circulators for that priority.
  4. Calculate the target temperature. Begin firing only if sensor temperature is below target.
  5. Wait for the closure switch.
  6. Run the blower at purge speed for prepurge.
  7. Check the min air flow switch.
  8. After prepurge, move to ignition speed.
  9. Energize the gas valve and ignition spark for the ignition period.
  10. Turn off the spark and use the flame rod to check for flame signal.

Applies to: SVF Series 1 firing sequence

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 68. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.