Weil-McLain · Boiler · Pump/purge

Call-for-heat pump and damper sequence

ECO Tec Series 3

What happens, in order

  1. Standby no call for heat, outputs off.
  2. Call for heat closes a terminal (TT).
  3. Pre-pump runs the associated pumps and AUX output for the PRE PUMP time.
  4. Pre-purge starts; SYSTEM DAMPER energizes at the start of pre-purge.
  5. Burner runs. LOCAL DAMPER energizes only while this boiler is attempting to fire.
  6. Burner off; post-purge runs.
  7. Post-pump runs the associated pumps and AUX output for the POST PUMP time.
  8. Return to standby. Dampers drop out after burner off and post-purge.

Timings and thresholds

ItemValue
Pre pumpOFF or 1-240 s (default OFF)
Post pump1-240 s (default 30 s; Combi default 10 s)

Applies to: ECO Tec Series 3 boilers with AUX pump/output and dampers configured

Models

ECO Tec Series 3 80/110/150/199

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 126. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.