Weil-McLain · Boiler · Heating
Burner firing cycle from call for heat to flame detection
What happens, in order
- On a call for heat, the display shows Blower ON with a blue light for space heating or a purple light for DHW.
- Start the max/min priority timers if more than one system is calling. The highest priority starts first.
- Start the circulators for that priority setup based on its settings.
- Calculate the target temperature. If the sensor temperature is below target, begin the firing sequence.
- Run the blower to ignition speed for prepurge.
- After prepurge times out, begin the ignition cycle: energize the gas valve and ignition spark.
- Keep the spark on for the ignition period, then turn it off and check for a flame signal at the electrode.
- When flame is detected, release the boiler to modulation for space heating or DHW.
- If no flame is detected, close the gas valve, run postpurge, and restart the cycle.
- If the priority timer runs out, switch to the next priority and start its timer.
Timings and thresholds
| Item | Value |
|---|---|
| Ignition retry after failed flame detection | After 5 failed attempts, the control waits 60 minutes before trying again |
Applies to: SlimFit 550/750 Series 3 single boiler with Control
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 66. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.