Weil-McLain · Boiler · Heating

Burner firing cycle from call for heat to flame detection

SlimFit Series 3

What happens, in order

  1. On a call for heat, the display shows Blower ON with a blue light for space heating or a purple light for DHW.
  2. Start the max/min priority timers if more than one system is calling. The highest priority starts first.
  3. Start the circulators for that priority setup based on its settings.
  4. Calculate the target temperature. If the sensor temperature is below target, begin the firing sequence.
  5. Run the blower to ignition speed for prepurge.
  6. After prepurge times out, begin the ignition cycle: energize the gas valve and ignition spark.
  7. Keep the spark on for the ignition period, then turn it off and check for a flame signal at the electrode.
  8. When flame is detected, release the boiler to modulation for space heating or DHW.
  9. If no flame is detected, close the gas valve, run postpurge, and restart the cycle.
  10. If the priority timer runs out, switch to the next priority and start its timer.

Timings and thresholds

ItemValue
Ignition retry after failed flame detectionAfter 5 failed attempts, the control waits 60 minutes before trying again

Applies to: SlimFit 550/750 Series 3 single boiler with Control

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 66. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.