Weil-McLain · Boiler · Other

Blower speed check firing order

ECO Tec Series 3

What happens, in order

  1. Select LOW firing rate and record blower rpm.
  2. Select IGNITION firing rate and record blower rpm.
  3. Select HIGH firing rate and record blower rpm.
  4. Compare each reading with the matching figure table and contact the factory if out of range.

Timings and thresholds

ItemValue
Blower rpm tolerancewithin 50 rpm of table value

Applies to: ECO Tec Series 3 gas boilers

Models

80110150199

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 142-143. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.