Weil-McLain · Boiler · Pump/purge

AUX PUMP/OUTPUT timing with ANY TT INPUT or ANY BURNER DEMAND

SVF Series 1

What happens, in order

  1. Standby output off.
  2. Input closes (TT call) or a burner demand starts: pre-pump begins, output on for ANY TT INPUT options.
  3. Pre-purge runs with the burner off; output is on for ANY BURNER DEMAND and DAMPER CONTROL options.
  4. Burner runs; output stays on.
  5. Heat call ends post-purge runs; output stays on until post-purge is done.
  6. Post-pump runs; output stays on for the post-pump time.
  7. Output drops out and the boiler returns to standby.

Applies to: Auxiliary pump/output relay behavior

Models

SVF 1500-3000

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 78. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.