Weil-McLain · Boiler · Pump/purge

AUX PUMP/OUTPUT start, run and stop

SlimFit Series 2

What happens, in order

  1. In standby with no heat call, the AUX output stays off.
  2. For ANY TT INPUT options, the output energizes when an input on this boiler closes.
  3. For ANY TT INPUT BY ITS PRIORITY option, the output energizes only if the closed input's priority has RUN AUX PUMP/OUTPUT set to YES.
  4. For burner demand options, the output energizes when the boiler gets a heat call and starts pre-purge.
  5. The output stays energized through burner running and post-purge.
  6. The output de-energizes after post-purge and post-pump are finished, or after the burner is off and post-purge is complete for BURNER DEMAND.

Applies to: SlimFit SF1000-SF2000 Series 2 boilers, AUX PUMP/OUTPUT operation

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual 550-100-561/1225, p. 72. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.