Viessmann · Boiler · Startup

Vitotronic 300 GW2 commissioning order

Vitotronic 300

What happens, in order

  1. Check that the heating circuit assignment stickers are on the correct spots on the control unit.
  2. Check the fixed high limit with the TÜV TEST button.
  3. Select the display language if needed.
  4. Set the LON participant number and update the LON participant list (LON systems only).
  5. Run the LON participant check (LON systems only).
  6. Match the control unit to the system type in coding 2.
  7. Test the relay outputs and check the sensors.
  8. Match the coding addresses to the modulating burner.
  9. Set the heating curves and room temperatures.

Applies to: Vitotronic 300 GW2 control units, order no. 7134 555, 7143 156, 7511 362

Models

Vitotronic 300Model GW2

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 64-71. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.