Vitotronic 200 start-up procedure (steps 1 to 5)
What happens, in order
- Check that the electrical connections match the system type (see System Components in Additional Information).
- Confirm the heating circuit assignment labels are in the correct fields on the programming unit. Circuit 1 has no mixing valve; circuit 2 has a mixing valve.
- Select the heating circuit to set first. The selected circuit button lights.
- Set the display language if needed (press the info button to show outdoor temperature, then choose the language and confirm).
- Match the coding addresses to the heating system equipment using the coding procedure.
- Set the normal and reduced room temperatures for each heating circuit.
- Set the heating curve slope and shift for each heating circuit.
- Set the boiler water high limit (coding 06) or supply high limit (coding C6) in coding level 1.
- Set the minimum supply temperature for the mixing valve circuit (coding C5) in coding level 1.
- Set the differential temperature for the mixing valve circuit (coding 05) in coding level 2.
Timings and thresholds
| Item | Value |
|---|---|
| Normal room temperature setpoint auto-accepted | approx. 2 seconds after adjusting |
| Enter coding level 1 or 2 (button hold) | approx. 2 seconds |
| Exit coding level (button hold) | approx. 1 second |
Applies to: Vitotronic 200 Model KW2 boiler control
Models
KW2
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 Si service instructions, p. 16-22. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.