Viessmann · Boiler · Pump/purge
Venting program sequence
What happens, in order
- Close the gas shut-off valve and switch the control unit on.
- Activate the venting program from the service menu.
- The circulation pump switches on and off alternately in 30 second intervals.
- The burner stays off during the venting program.
- Check the system pressure when done.
- End the function with OK.
Timings and thresholds
| Item | Value |
|---|---|
| Pump on/off interval | 30 s each |
| Total venting program duration | 20 min |
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
Models
4557160199
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, pp. 16-17. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.