Viessmann · Boiler · Pump/purge

Venting (bleeding) program

Vitodens 200-W B2HB

What happens, in order

  1. Close the gas shut-off valve and switch the control unit ON.
  2. Start the venting program from service functions.
  3. The circulation pump runs alternately ON and OFF for 30 seconds each over 20 minutes.
  4. The burner stays OFF during the venting program.
  5. After the program, check the system pressure.

Timings and thresholds

ItemValue
Pump ON and OFF cycle30 seconds each
Total venting program duration20 minutes

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Models

B2HB 45B2HB 57B2HB 160B2HB 199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.