Viessmann · Boiler · Pump/purge

Venting (air bleed) program

Vitodens 200-W

What happens, in order

  1. Activate the venting program as described in the heating system venting section.
  2. Circulation pump runs alternately on and off, 30 seconds at a time.
  3. Burner stays off during the program.
  4. Program turns off automatically after 20 minutes.
  5. Coding address 2F returns to 0.

Timings and thresholds

ItemValue
Pump on/off cycle30 seconds each
Total program length20 minutes

Codes you may see during this

2F:1

Applies to: Heating system air bleed

Models

B2HB 45B2HB 57B2HB 160B2HB 199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service manual, p. 89-90. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.