Update LON participant list for Vitocontrol-S cascade control
What happens, in order
- Complete all communication connections first.
- Confirm the Vitocontrol-S is coded as the error manager (default), see Vitocontrol-S manual address 79:01.
- Set a unique LON participant number on each Versatronik 502 gateway using the rotary dial, with no duplicates.
- Press OK and the lined Menu button together to open the Service menu, then press OK.
- Arrow down to Service Functions and press OK.
- On the Service Functions screen, highlight Subscriber Check and press OK.
- Arrow down to Delete List? and press OK to update the participant list.
- Wait for the LON participant information to update for the boiler controls and other Versatronik LON devices.
- Do not re-enter Subscriber Check too early, or the screen will show No Subscriber.
Applies to: Vitocontrol-S cascade control with Versatronik 502 gateways
Models
Versatronik 502Versatronik 502D
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 502 MODBUS manual, p. 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.