Viessmann · Boiler · Other

Update LON participant list for Vitocontrol-S cascade control

Versatronik 502Versatronik 502D

What happens, in order

  1. Complete all communication connections first.
  2. Confirm the Vitocontrol-S is coded as the error manager (default), see Vitocontrol-S manual address 79:01.
  3. Set a unique LON participant number on each Versatronik 502 gateway using the rotary dial, with no duplicates.
  4. Press OK and the lined Menu button together to open the Service menu, then press OK.
  5. Arrow down to Service Functions and press OK.
  6. On the Service Functions screen, highlight Subscriber Check and press OK.
  7. Arrow down to Delete List? and press OK to update the participant list.
  8. Wait for the LON participant information to update for the boiler controls and other Versatronik LON devices.
  9. Do not re-enter Subscriber Check too early, or the screen will show No Subscriber.

Applies to: Vitocontrol-S cascade control with Versatronik 502 gateways

Models

Versatronik 502Versatronik 502D

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 502 MODBUS manual, p. 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.