Viessmann · Boiler · Heating

Two-stage burner switching with gradient method

Versatronik 200

What happens, in order

  1. Stage 1 starts when boiler temperature drops below the boiler setpoint.
  2. Stage 1 stops when the setpoint is exceeded by the hysteresis.
  3. Stage 2 is blocked for the boiler on-delay after stage 1 starts.
  4. Stage 2 is enabled when the temperature is 5 K below setpoint and the on-delay has expired.
  5. Stage 2 stops when the setpoint is exceeded by the hysteresis.
  6. With gradient on, stage 1 stops early when stage 2 is enabled and the temperature exceeds setpoint plus hysteresis plus stage 2 hysteresis.

Timings and thresholds

ItemValue
Boiler on-delay (00 setting)10 sec
Stage 2 enable point5 K below setpoint
Hysteresis stage 22 K to 20 K, standard 2 K

Applies to: Versatronik 200, two-stage burners or two burner relays (A6 and A7)

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 141. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.