Viessmann · Boiler · Heating
Two-stage burner switching with gradient method
What happens, in order
- Stage 1 starts when boiler temperature drops below the boiler setpoint.
- Stage 1 stops when the setpoint is exceeded by the hysteresis.
- Stage 2 is blocked for the boiler on-delay after stage 1 starts.
- Stage 2 is enabled when the temperature is 5 K below setpoint and the on-delay has expired.
- Stage 2 stops when the setpoint is exceeded by the hysteresis.
- With gradient on, stage 1 stops early when stage 2 is enabled and the temperature exceeds setpoint plus hysteresis plus stage 2 hysteresis.
Timings and thresholds
| Item | Value |
|---|---|
| Boiler on-delay (00 setting) | 10 sec |
| Stage 2 enable point | 5 K below setpoint |
| Hysteresis stage 2 | 2 K to 20 K, standard 2 K |
Applies to: Versatronik 200, two-stage burners or two burner relays (A6 and A7)
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 installation and operating manual, p. 141. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.