Viessmann · Boiler · Ignition

Two-stage burner start with external contacts

Vitotronic 100GC1

What happens, in order

  1. Close the contact on plug aVD terminals 1 and 2. The 1st stage burner starts.
  2. If the boiler water falls below minimum temperature, the 2nd stage starts to hold it.
  3. Close the contact on plug aVD terminals 2 and 3 to start the 2nd stage. Both stages run.
  4. Limit boiler water temperature with coding 06 if set below the mechanical high limit R.

Timings and thresholds

ItemValue
2nd stage switch-off ahead of 1st stage2 K sooner

Applies to: Two-stage burner

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.