Viessmann · Boiler · Ignition
Two-stage burner start with external contacts
What happens, in order
- Close the contact on plug aVD terminals 1 and 2. The 1st stage burner starts.
- If the boiler water falls below minimum temperature, the 2nd stage starts to hold it.
- Close the contact on plug aVD terminals 2 and 3 to start the 2nd stage. Both stages run.
- Limit boiler water temperature with coding 06 if set below the mechanical high limit R.
Timings and thresholds
| Item | Value |
|---|---|
| 2nd stage switch-off ahead of 1st stage | 2 K sooner |
Applies to: Two-stage burner
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.