Two-boiler cascade example with modulating burners

Vitocontrol-S VD2/CT3/CM2

What happens, in order

  1. Boiler 1 and boiler 2 are each 100 kW, with basic load set to 33 percent (see page 96).
  2. Gross calorific strategy (coding 3C 0): boilers start at low output and both run at low load together before the second boiler is fully loaded.
  3. Net calorific strategy 1 (coding 3C 1): one boiler carries load up to its maximum output before the second boiler starts.
  4. Net calorific strategy 2 the second boiler is started late and shut down late, reflecting its start-up and shutdown integrals.

Applies to: Two-boiler system with modulating burners

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 128. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.