Two-boiler cascade example with modulating burners
What happens, in order
- Boiler 1 and boiler 2 are each 100 kW, with basic load set to 33 percent (see page 96).
- Gross calorific strategy (coding 3C 0): boilers start at low output and both run at low load together before the second boiler is fully loaded.
- Net calorific strategy 1 (coding 3C 1): one boiler carries load up to its maximum output before the second boiler starts.
- Net calorific strategy 2 the second boiler is started late and shut down late, reflecting its start-up and shutdown integrals.
Applies to: Two-boiler system with modulating burners
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 128. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.