Viessmann · Boiler · Startup
Therm-Control start-up flow limit (single boiler)
What happens, in order
- Therm-Control acts on the heating control unit or heating circuit pumps if the set temperatures are not reached at the Therm-Control sensor.
- During start-up (commissioning, or after a night or weekend shutdown), reduce the boiler water flow rate.
- If the boiler is controlled by Vitotronic 300 GW2/GW2B or by Vitotronic 200-H, no extra on-site protection is needed.
- If flow cannot be reduced (for example older systems), contact Viessmann for other piping layouts.
- No minimum return water temperature is required; no shunt pump or boiler circuit pump is needed.
Timings and thresholds
| Item | Value |
|---|---|
| Boiler water flow reduction during start-up | at least 50% |
Applies to: Single boiler system with Therm-Control
Models
Vitorond 200 VD2A 125 to 270
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A Technical Data Manual, p. 19. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.