Viessmann · Boiler · Startup

Therm-Control start-up flow limit (single boiler)

Vitorond 200 VD2A

What happens, in order

  1. Therm-Control acts on the heating control unit or heating circuit pumps if the set temperatures are not reached at the Therm-Control sensor.
  2. During start-up (commissioning, or after a night or weekend shutdown), reduce the boiler water flow rate.
  3. If the boiler is controlled by Vitotronic 300 GW2/GW2B or by Vitotronic 200-H, no extra on-site protection is needed.
  4. If flow cannot be reduced (for example older systems), contact Viessmann for other piping layouts.
  5. No minimum return water temperature is required; no shunt pump or boiler circuit pump is needed.

Timings and thresholds

ItemValue
Boiler water flow reduction during start-upat least 50%

Applies to: Single boiler system with Therm-Control

Models

Vitorond 200 VD2A 125 to 270

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A Technical Data Manual, p. 19. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.